L1-06D.22 – ITI Format

L1-06D.22 – ITI Format Format type that includes a five digit account number, one digit event identifier, and three digit user/zone number Examples: 12-345 A001  12-345 W001 12-345 R001 Play the Sound...

L1-06D.21 – DMP Format

L1-06D.21 – DMP Format Uses Synchronous Data Link Control (SDLC), a networking communication format invented by IBM. Reports up to 47 Characters including keypad displayed information: Example:    1234 – Area: 01 – Main Bldg   Open: User 101 John Doe Play the...

L1-06D.20 – Modem IIIa2 and Modem IIe Format

L1-06D.20 – Modem IIIa2 and Modem IIe Format Formats that are proprietary to Bosch (formerly Radionics and Detection System) panels. Four to ten digit account number, one digit identifier, three digit user/zone number, point text. Examples:   1234  A  001  Alarm...

L1-06D.19 – SIA Format

L1-06D.19 – SIA Format Uses binary frequency shift keying (BFSK). Format may also include a number (1, 3, 8, 20) that represents how many signals are sent during each phone call.  Examples:                         FA1  BA03  OP006 1 Includes:  Four digit account...

L1-06D.18 – Contact ID Format

L1-06D.18 – Contact ID Format Uses DTMF (touch tones) Includes a four digit account number, one digit event code, three digit event identifier, two digit area, three digit zone/user number. Example: 1234 E 134 01 001      and     1234 R 134 01 001 Where: 1234 =...